Responding to SRF cavity trips
- Determine which cavity has tripped
- MPS failed device dialogue box
- RF main page or any cavity status page
- Navigate to the LLRF interlock detail page
- If any of the following interlocks are present do not reset the latch or the cavity, skip directly to last step
- PLC
- Spark Detectors
- Excessive Cavity Field
- Tuner Fault
- CCG Low/High
- Bias Tee Low/High
- If the cavity is interlocked on something other than the above list reset the interlock and restart the cavity
- If the cavity trips off again on Cavity Field Low you may have to perform a reduce recover on the surrounding cavities
- Call SRF personnel on call