User Tools

Site Tools


task:srf_trips

This is an old revision of the document!


Responding to SRF cavity trips

  1. Determine which cavity has tripped
    1. MPS failed device dialogue box
    2. RF main page or any cavity status page
  2. Navigate to the LLRF interlock detail page
  3. If any of the following interlocks are present do not reset the latch or the cavity, skip directly to last step
    1. PLC
    2. Spark Detectors
    3. Excessive Cavity Field
    4. Tuner Fault
    5. CCG Low/High
    6. Bias Tee Low/High
  4. If the cavity is interlocked on something other than the above list reset the interlock and restart the cavity
  5. If the cavity trips off again on Cavity Field Low you may have to perform a reduce recover on the surrounding cavities
  6. Call SRF personnel on call
task/srf_trips.1727876785.txt.gz · Last modified: 2024/10/02 09:46 by harvey

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki