Recovering HPECR from Gate Valves Closing

If MPS tripped due to gate valves closing, please follow the HPECR recovery instructions:

  • On HPECR operator page, Open Gate Valve FE_ISRC2:BGV_D0675.
  • Go to Microwave Amp. in the 18GHz Microwave Transmitter section.
  • On the Microwave Amp page:
    1. Check on HPECR Vacuum page and ensure that the BCCG's are okay
    2. Reset all interlocks / safety interlocks
    3. Turn on PLC commands
    4. Reset all interlocks / safety interlocks again
    5. Turn on BEAM power supply ISC2_HVP_D0652
    6. Reset “RF OUTPUT Set point” to ZERO
    7. Turn ON RF output
    8. Recover the RF output power to where it was by 100V/step.
  • Go back to the HPECR operator page, turn on both source high voltage and platform high voltage HVP D0652 and HVP D0677.
  • Turn back on the acceleration column puller PSEL D0678.