If any of the following interlocks are present do not reset the latch or the cavity, skip directly to last step. See image below
PLC
Spark Detectors
Excessive Cavity Field
Tuner Fault
CCG Low/High
Bias Tee Low/High
If the cavity is interlocked on something other than the above list reset the interlock and restart the cavity
If the cavity trips off again or trips off on Cavity Field Low you may have to perform a reduce recover on the surrounding cavities. If cavity trips off again skip to last step