task:srf_trips [2024/10/02 10:17] – harvey | task:srf_trips [2024/10/27 10:14] (current) – changed header level pirkola | ||
---|---|---|---|
Line 5: | Line 5: | ||
- RF main page or any cavity status page | - RF main page or any cavity status page | ||
- Navigate to the LLRF interlock detail page | - Navigate to the LLRF interlock detail page | ||
- | - If any of the following interlocks are present do not reset the latch or the cavity, skip directly to last step | + | - If any of the following interlocks are present do not reset the latch or the cavity, skip directly to last step. See image below |
- PLC | - PLC | ||
- Spark Detectors | - Spark Detectors | ||
Line 13: | Line 13: | ||
- Bias Tee Low/High | - Bias Tee Low/High | ||
- If the cavity is interlocked on something other than the above list reset the interlock and restart the cavity | - If the cavity is interlocked on something other than the above list reset the interlock and restart the cavity | ||
- | - If the cavity trips off again on Cavity Field Low you may have to perform a reduce recover on the surrounding cavities. If cavity trips off again skip to last step | + | - If the cavity trips off again or trips off on Cavity Field Low you may have to perform a reduce recover on the surrounding cavities. If cavity trips off again skip to last step |
- Call SRF personnel on call | - Call SRF personnel on call | ||
- | ====== Links/Media ====== | + | ===== Links/Media ===== |
+ | * [[https:// | ||
* {{task: | * {{task: | ||