| ====== Responding to SRF cavity trips ====== | ====== Responding to SRF cavity trips ====== | ||
| - | - Determine which cavity | + | - Determine which cavity |
| + | - MPS failed device dialogue box | ||
| + | - RF main page or any cavity status page | ||
| + | - Navigate to the LLRF interlock detail page | ||
| + | - If any of the following interlocks are present do not reset the latch or the cavity, skip directly to last step. See image below | ||
| + | - PLC | ||
| + | - Spark Detectors | ||
| + | - Excessive Cavity Field | ||
| + | - Tuner Fault | ||
| + | - CCG Low/High | ||
| + | - Bias Tee Low/High | ||
| + | - If the cavity is interlocked on something other than the above list reset the interlock and restart the cavity | ||
| + | - If the cavity trips off again or trips off on Cavity Field Low you may have to perform a reduce recover on the surrounding cavities. If cavity trips off again skip to last step | ||
| + | - Call SRF personnel on call | ||
| + | |||
| + | ===== Links/Media ===== | ||
| + | * [[https:// | ||
| + | * {{task: | ||
| + | |||
| + | |||
| + | |||
| + | |||
| + | |||
| + | |||
| + | |||
| + | |||
| + | |||