User Tools

Site Tools


task:opening_area

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
task:opening_area [2024/10/22 16:24] paintertask:opening_area [2024/10/22 17:47] (current) painter
Line 1: Line 1:
  ======= Opening Target Facility Area =======  ======= Opening Target Facility Area =======
  
-== Steps == +== Open == 
   - Turn the Beam/Chopper off   - Turn the Beam/Chopper off
   - On the Main Magnets page, turn Dipole D5578 off on BBS/FFS tab; this will take a moment to ramp down to 0 A.   - On the Main Magnets page, turn Dipole D5578 off on BBS/FFS tab; this will take a moment to ramp down to 0 A.
Line 9: Line 9:
   - Operator goes to room and starts a survey for entire area, or specific spot if required.   - Operator goes to room and starts a survey for entire area, or specific spot if required.
   - After room fully surveyed and opened, on the PPS rack, turn the key for the opened room to Regulated Access.    - After room fully surveyed and opened, on the PPS rack, turn the key for the opened room to Regulated Access. 
 +
 +== Close == 
 +
 +  - On the PPS rack, turn the room key to Search Survey.
 +  - Reset the warning alarms in area through the PPS rack.
 +  - Perform search and evict of area.
 +  - Once all target areas are secured, turn the Target RSS Ready for Beam key to Yes. Wait a minute for the Target Facility lights to stop flashing and turn solid red.
 +  - Ensure you are in required machine mode for beam.
 +  - Turn the Linac ACS key back to Beam Permit.
 +  - On the Main Magnets page, cycle the D5578 dipole to 90 A on the BBS/FFS tab:
 +      - Copy the current setpoint value. 
 +      - Turn on D5578 dipole (this will take a few seconds to go green).
 +      - When the dipole is on, input 90 A into the setpoint value.
 +      - When done ramping to 90 A, paste the original setpoint value.
 +      - Wait for dipole to ramp to original value.
 +  - On the MPS Operator page, turn the E-Bends on.
 +  - On the Main Magnets page check that the E-Bends setpoint and readback values match on the V-LEBT tab.
 +  - On the MPS Operator page, set configuration according to MPS Device Configuration Guideline.
 +  - Check and clear all set MPS devices. 
 +  - Start the Chopper.
 +
 +
 +
 +===== Links =====
 +  * [[clist>154|Search-and-Evict Procedure for the FRIB Target Hall]]
 +  * [[dcc>WBS=S30103&Sub=RC&SN=008105|MPS Device Configuration Guideline]]
 +
      
task/opening_area.1729628687.txt.gz · Last modified: 2024/10/22 16:24 by painter