-======= Opening EXP Vault Area =======+ ======= Opening Target Facility Area =======
  
-== Steps == +== Open ==  
 +  - Turn the Beam/Chopper off 
 +  - On the Main Magnets page, turn Dipole D5578 off on BBS/FFS tab; this will take a moment to ramp down to 0 A. 
 +  - On the MPS Operator page, turn E-Bends off.  
 +  - On the PPS rack, turn the Linac ACS key to Beam Permit. 
 +  - On the PPS rack, turn the key for Target RSS Ready For Beam to Off.  
 +  - Operator goes to room and starts a survey for entire area, or specific spot if required. 
 +  - After room fully surveyed and opened, on the PPS rack, turn the key for the opened room to Regulated Access. 
  
 +== Close == 
 +
 +  - On the PPS rack, turn the room key to Search Survey.
 +  - Reset the warning alarms in area through the PPS rack.
 +  - Perform search and evict of area.
 +  - Once all target areas are secured, turn the Target RSS Ready for Beam key to Yes. Wait a minute for the Target Facility lights to stop flashing and turn solid red.
 +  - Ensure you are in required machine mode for beam.
 +  - Turn the Linac ACS key back to Beam Permit.
 +  - On the Main Magnets page, cycle the D5578 dipole to 90 A on the BBS/FFS tab:
 +      - Copy the current setpoint value. 
 +      - Turn on D5578 dipole (this will take a few seconds to go green).
 +      - When the dipole is on, input 90 A into the setpoint value.
 +      - When done ramping to 90 A, paste the original setpoint value.
 +      - Wait for dipole to ramp to original value.
 +  - On the MPS Operator page, turn the E-Bends on.
 +  - On the Main Magnets page check that the E-Bends setpoint and readback values match on the V-LEBT tab.
 +  - On the MPS Operator page, set configuration according to MPS Device Configuration Guideline.
 +  - Check and clear all set MPS devices. 
 +  - Start the Chopper.
 +
 +
 +
 +===== Links =====
 +  * [[clist>154|Search-and-Evict Procedure for the FRIB Target Hall]]
 +  * [[dcc>WBS=S30103&Sub=RC&SN=008105|MPS Device Configuration Guideline]]
  
-  - Turn the Beam/Chopper off. 
-  - Inset FC D1102.  
-  - On the MPS Operator page, turn E-Bends off. 
-  - On the EXP Launcher, go to T-Hall/EXP Operator page. Insert Beam Stop for required area.  
-  - On the PPS rack, turn the key for Linac AC to Beam Permit. Then turn Experimental Vault ready for Beam key to off.  
      
task/opening_area.1729628129.txt.gz · Last modified: 2024/10/22 16:15 by painter

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki