User Tools

Site Tools


task:opening_area

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Next revision
Previous revision
task:opening_area [2024/10/08 10:08] – created paintertask:opening_area [2024/10/22 17:47] (current) painter
Line 1: Line 1:
-== Steps ==  + ======= Opening Target Facility Area ======= 
-  - Turn the Beam/Chopper off. + 
-  - Go to Main Magnets page through FRIB Launch. Go go the BBS/FFS page. Turn Dipole D5578 off; this will take a moment to ramp down to 0 A. +== Open ==  
-  - On MPS Operator page, turn E-Bends off. +  - Turn the Beam/Chopper off 
-  - On the PPS machinefirst turn the Linac ACS key to Beam Permit. Then, turn the key for Target RSS Ready For Beam to Off. +  - On the Main Magnets page, turn Dipole D5578 off on BBS/FFS tab; this will take a moment to ramp down to 0 A. 
-  - Operator goes to room and starts a survey for entire area, or specific spot if required.  +  - On the MPS Operator page, turn E-Bends off.  
-  - After room is opened, on the PPS rack, flip the key for the opened room to Regulated Access. +  - On the PPS rack, turn the Linac ACS key to Beam Permit. 
 +  - On the PPS rack, turn the key for Target RSS Ready For Beam to Off.  
 +  - Operator goes to room and starts a survey for entire area, or specific spot if required. 
 +  - After room fully surveyed and opened, on the PPS rack, turn the key for the opened room to Regulated Access.  
 + 
 +== Close ==  
 + 
 +  - On the PPS rack, turn the room key to Search Survey. 
 +  - Reset the warning alarms in area through the PPS rack. 
 +  - Perform search and evict of area. 
 +  - Once all target areas are secured, turn the Target RSS Ready for Beam key to Yes. Wait a minute for the Target Facility lights to stop flashing and turn solid red. 
 +  - Ensure you are in required machine mode for beam. 
 +  - Turn the Linac ACS key back to Beam Permit. 
 +  - On the Main Magnets page, cycle the D5578 dipole to 90 A on the BBS/FFS tab: 
 +      - Copy the current setpoint value.  
 +      - Turn on D5578 dipole (this will take a few seconds to go green). 
 +      - When the dipole is on, input 90 A into the setpoint value. 
 +      - When done ramping to 90 A, paste the original setpoint value. 
 +      - Wait for dipole to ramp to original value. 
 +  - On the MPS Operator page, turn the E-Bends on. 
 +  - On the Main Magnets page check that the E-Bends setpoint and readback values match on the V-LEBT tab. 
 +  - On the MPS Operator page, set configuration according to MPS Device Configuration Guideline. 
 +  - Check and clear all set MPS devices.  
 +  - Start the Chopper. 
 + 
 + 
 + 
 +===== Links ===== 
 +  * [[clist>154|Search-and-Evict Procedure for the FRIB Target Hall]] 
 +  * [[dcc>WBS=S30103&Sub=RC&SN=008105|MPS Device Configuration Guideline]] 
 + 
 +  
task/opening_area.1728396494.txt.gz · Last modified: 2024/10/08 10:08 by painter

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki