User Tools

Site Tools


task:hpecr_recovery

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
task:hpecr_recovery [2025/03/18 17:01] paintertask:hpecr_recovery [2025/03/18 17:03] (current) painter
Line 10: Line 10:
        - Turn on PLC commands        - Turn on PLC commands
        - Reset all interlocks / safety interlocks again        - Reset all interlocks / safety interlocks again
-       - Turn on BEAM power supply ISC2_HVP_D0652+       - Turn on BEAM power supply ISC2_HVP_D0652 & ISC2_HVP_D0677 
 +       - Turn back on the acceleration column puller PSEL D0678.
        - Reset "RF OUTPUT Set point" to ZERO        - Reset "RF OUTPUT Set point" to ZERO
        - Turn ON RF output        - Turn ON RF output
        - Recover the RF output power to where it was by 100V/step.         - Recover the RF output power to where it was by 100V/step. 
-      + 
-    *Go back to the HPECR operator page, turn on both source high voltage and platform high voltage HVP D0652 and HVP D0677. +
-    *Turn back on the acceleration column puller PSEL D0678.+
  
  
task/hpecr_recovery.1742331700.txt.gz · Last modified: 2025/03/18 17:01 by painter