info:dcct_info
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revision | |||
| info:dcct_info [2024/09/30 09:43] – removed - external edit (Unknown date) 127.0.0.1 | info:dcct_info [2024/09/30 09:43] (current) – ↷ Page moved from dcct_info to info:dcct_info pirkola | ||
|---|---|---|---|
| Line 1: | Line 1: | ||
| + | ====== DCCT info page ====== | ||
| + | |||
| + | ==== Disclaimer ==== | ||
| + | DCCTs are our primary way of monitoring the current on our big magnets, important magnets; these include the FS2 dipoles, BDS dipoles, and the dipoles in the Fragment Separator. You will note that there is no Enterprise training competency, or course, on this subject, meaning that the only record of completion that we have is on the OIC training checklist. This also means that the only training material that we have is a couple of DCC documents that weren' | ||
| + | |||
| + | ==== Current practice ==== | ||
| + | Currently operators are setting the DCCTs using the following steps: | ||
| + | - Disarm DCCT, note the magnet setpoint | ||
| + | - Set the negative and positive thresholds to 0.2% pf current magnet setpoint | ||
| + | - Clear the DCCT alarm, arm the DCCT | ||
| + | |||
| + | |||
| + | ==== Setting the values ==== | ||
| + | Most operators use their phone calculator or their computer calculator to make this calculation, | ||
| + | * (Current magnet setpoint) * 0.002 = threshold | ||
| + | |||
| + | ===== Links ===== | ||
| + | |||
| + | * [[ops> | ||